Operation mode
Freq< + df/dt
Table continues on next page
Protection functions
Description
A consecutive operation is enabled between the
protection methods. When the measured
frequency is below the set value of the
value Freq< setting, the frequency gradient
protection is enabled. After the frequency has
dropped below the set value, the frequency
gradient is compared to the set value of the
value df/dt setting. When the frequency gradient
exceeds the set value, the module activates the
START and STR_FRG outputs. The time
characteristic is according to DT. When the
operation timer has reached the value set by the
Operate Tm df/dt setting, the OPERATE and
OPR_FRG outputs are activated. If the frequency
gradient restores before the module operates,
the reset timer is activated. If the timer reaches
Reset delay Tm df/dt setting,
the value set by the
the operate timer resets and the START and
STR_FRG outputs are deactivated. The
OPR_UFRQ output is not active when this
operation mode is used.