Section 4
Protection functions
Table 302:
DEFHPDEF Group settings
Parameter
Start value
Start value Mult
Directional mode
Time multiplier
Operating curve type
Type of reset curve
Operate delay time
Operation mode
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
Enable voltage limit
Table 303:
DEFHPDEF Non group settings
Parameter
Operation
Reset delay time
Minimum operate time
Allow Non Dir
Measurement mode
Min operate current
Min operate voltage
Correction angle
Table continues on next page
300
Values (Range)
Unit
0.10...40.00
xIn
0.8...10.0
1=Non-directional
2=Forward
3=Reverse
0.05...15.00
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
1=Immediate
2=Def time reset
3=Inverse reset
40...200000
ms
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
-179...180
deg
0...180
deg
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
0=False
1=True
Values (Range)
Unit
1=on
5=off
0...60000
ms
40...60000
ms
0=False
1=True
1=RMS
2=DFT
3=Peak-to-Peak
0.005...1.000
xIn
0.01...1.00
xUn
0.0...10.0
deg
Step
Default
0.01
0.10
0.1
1.0
2=Forward
0.01
1.00
15=IEC Def. Time
1=Immediate
10
40
1=Phase angle
1
-90
1
80
1
80
1
80
1
80
0.001
0.010
1=True
Step
Default
1=on
1
20
1
40
0=False
2=DFT
0.001
0.005
0.01
0.01
0.1
0.0
1YHT530004D05 D
Description
Start value
Multiplier for scaling the start value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Selection of reset curve type
Operate delay time
Operation criteria
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
Enable voltage limit
Description
Operation Off / On
Reset delay time
Minimum operate time for IDMT curves
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Angle correction