ABB RED615 Technical Manual page 203

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Parameter
Values (Range)
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage Mem time
Pol quantity
Table 206:
DPHHPDOC Non group settings
Parameter
Values (Range)
Operation
Reset delay time
Minimum operate time
Allow Non Dir
Measurement mode
Min operate current
Min operate voltage
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Num of start phases
615 series
Technical Manual
Unit
0...90
deg
0...90
deg
0...90
deg
0...90
deg
0...3000
ms
-2=Pos. seq. volt.
1=Self pol
4=Neg. seq. volt.
5=Cross pol
Unit
1=on
5=off
0...60000
ms
20...60000
ms
0=False
1=True
1=RMS
2=DFT
3=Peak-to-Peak
0.01...1.00
xIn
0.01...1.00
xUn
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
1=1 out of 3
2=2 out of 3
3=3 out of 3
Step
Default
1
80
1
80
1
80
1
80
1
40
5=Cross pol
Step
Default
1=on
1
20
1
20
0=False
2=DFT
0.01
0.01
0.01
0.01
28.2000
0.1217
2.00
29.10
1.0
1=1 out of 3
Section 4
Protection functions
Description
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage memory time
Reference quantity used to determine
fault direction
Description
Operation Off / On
Reset delay time
Minimum operate time for IDMT curves
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer
programmable curve
Parameter D for customer
programmable curve
Parameter E for customer programmable
curve
Number of phases required for operate
activation
197