Section 4
Protection functions
352
LV side (A): I
= 5 MVA / (1.732 × 10.5 kV) = 274.9 A
nT_B
So the settings for CT ratio Corrections at HV (A) and LV (B) side are:
CT ratio Correction (A) = 200 A / 144.3 A = 1.386
CT ratio Correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as "Type 1"
and "Type 2".
If the positive directions of the winding 1 and winding 2 IED currents are
opposite, the CT connection type setting parameter is "Type 1". The
connection examples of "Type 1" are as shown in the
186.
If the positive directions of the winding 1 and winding 2 IED currents equate,
the CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in the
The default value of the CT connection type setting is "Type 1".
1YHT530004D05 D
Figure 185
and
Figure 187
and
Figure
188.