ABB RED615 Technical Manual page 627

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Parameter
Values (Range)
Opening time Cor
Closing time Cor
Spring charge time
Counter initial Val
Alarm Op number
Lockout Op number
Current exponent
Difference Cor time
Alm Acc currents Pwr
LO Acc currents Pwr
Ini Acc currents Pwr
Directional Coef
Initial CB Rmn life
Rated Op current
Rated fault current
Op number rated
Op number fault
Life alarm level
Pressure alarm time
Pres lockout time
Inactive Alm days
Ini inactive days
Inactive Alm hours
615 series
Technical Manual
Unit
0...100
ms
0...100
ms
0...60000
ms
0...9999
0...9999
0...9999
0.00...2.00
-10...10
ms
0.00...20000.00
0.00...20000.00
0.00...20000.00
-3.00...-0.50
0...9999
100.00...5000.00
A
500.00...75000.00
A
1...99999
1...10000
0...99999
0...60000
ms
0...60000
ms
0...9999
0...9999
0...23
h
Condition monitoring functions
Step
Default
1
10
1
10
10
1000
1
0
1
200
1
300
0.01
2.00
1
5
0.01
2500.00
0.01
2500.00
0.01
0.00
0.01
-1.50
1
5000
0.01
1000.00
0.01
5000.00
1
10000
1
1000
1
500
1
10
10
10
1
2000
1
0
1
0
Section 7
Description
Correction factor for open travel time in ms
Correction factor for CB close travel time
in ms
Setting of alarm for spring charging time
of CB in ms
The operation numbers counter
initialization value
Alarm limit for number of operations
Lock out limit for number of operations
Current exponent setting for energy
calculation
Corr. factor for time dif in aux. and main
contacts open time
Setting of alarm level for accumulated
currents power
Lockout limit setting for accumulated
currents power
Initial value for accumulation energy (Iyt)
Directional coefficient for CB life
calculation
Initial value for the CB remaining life
Rated operating current of the breaker
Rated fault current of the breaker
Number of operations possible at rated
current
Number of operations possible at rated
fault current
Alarm level for CB remaining life
Time delay for gas pressure alarm in ms
Time delay for gas pressure lockout in ms
Alarm limit value of the inactive days
counter
Initial value of the inactive days counter
Alarm time of the inactive days counter
in hours