ABB RED615 Technical Manual page 101

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Parameter
Values (Range)
Value high limit
Value low limit
Value low low limit
Value deadband
Table 57:
mA input settings
Parameter
Values (Range)
Input mode
Input maximum
Input minimum
Value unit
Value maximum
Value minimum
Val high high limit
Value high limit
Value low limit
Value low low limit
Value deadband
615 series
Technical Manual
Unit
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
100...100000
Unit
1=Not in use
5=0..20mA
0...20
0...20
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
100...100000
Step
Default
10000.0
-10000.0
-10000.0
1000
Step
Default
1=Not in use
1
20
1
0
1=Dimensionless
10000.0
-10000.0
10000.0
10000.0
-10000.0
-10000.0
1000
Section 3
Basic functions
Description
Output value high warning limit for
supervision
Output value low warning limit for
supervision
Output value low alarm limit for
supervision
Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
Description
Analogue input mode
Maximum analogue input value for mA
or resistance scaling
Minimum analogue input value for mA or
resistance scaling
Selected unit for output value format
Maximum output value for scaling and
supervision
Minimum output value for scaling and
supervision
Output value high alarm limit for
supervision
Output value high warning limit for
supervision
Output value low warning limit for
supervision
Output value low alarm limit for
supervision
Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
95