ABB RED615 Technical Manual page 414

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
408
Vector group of the
Winding 1 type
transformer
ZNy1
ZN
Zy5
Z
Zyn5
Z
ZNyn5
ZN
ZNy5
ZN
Zy7
Z
Zyn7
Z
ZNyn7
ZN
ZNy7
ZN
Yy0
Y
Commissioning
The correct settings, which are CT connection type, Winding 1 type, Winding 2 type
and Clock number, for the connection group compensation can be verified by
monitoring the angle values I_ANGL_A1_B1, I_ANGL_B1_C1,
I_ANGL_C1_A1, I_ANGL_A2_B2, I_ANGL_B2_C2, I_ANGL_C2_A2,
I_ANGL_A1_A2, I_ANGL_B1_B2 and I_ANGL_C1_C2 while injecting the
current into the transformer. These angle values are calculated from the
compensated currents. See signal description from Monitored data table.
When a station service transformer is available, it can be used to provide current to
the high voltage side windings while the low voltage side windings are short-
circuited. This way the current can flow in both the high voltage and low voltage
windings. The commissioning signals can be provided by other means as well. The
minimum current to allow for phase current and angle monitoring is 0.015 I
GUID-5ACBF127-85A3-4E5E-A130-9F7206A2DB4C V1 EN
Figure 218:
Low voltage test arrangement. The three-phase low voltage source
can be the station service transformer.
The Tapped winding control setting parameter has to be set to "Not in use" to make
sure that the monitored current values are not scaled by the automatic adaptation to
the tap changer position. When only the angle values are required, the setting of
Tapped winding is not needed since angle values are not affected by the tap
changer position adaptation.
Winding 2 type
Clock number
y
Clk Num 1
y
Clk Num 5
yn
Clk Num 5
yn
Clk Num 5
y
Clk Num 5
y
Clk Num 7
yn
Clk Num 7
yn
Clk Num 7
y
Clk Num 7
y
Clk Num 0
1YHT530004D05 D
Zro A Elimination
Not needed
Not needed
Not needed
HV side
Not needed
Not needed
Not needed
HV side
Not needed
Not needed
.
r