ABB RED615 Technical Manual page 68

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 3
Basic functions
62
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 38:
Warning indications and codes
Warning indication
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
ACT error
Warning
GOOSE Rx. error
Warning
AFL error
Warning
Unack card comp.
Warning
Protection comm.
Warning
ARC1 cont. light
Warning
ARC2 cont. light
Warning
ARC3 cont. light
Warning
RTD card error,X130
Warning
RTD meas. error,X130
Warning code
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model.
21
Error in the Modbus communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the
file is missing.
28
Too many connections in the
configuration.
29
Error in the SMT connections.
30
Error in the GOOSE connections.
31
Error in the ACT connections.
32
Error in the GOOSE message receiving.
33
Analog channel configuration error.
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication.
85
A continuous light has been detected on
the ARC light input 1.
86
A continuous light has been detected on
the ARC light input 2.
87
A continuous light has been detected on
the ARC light input 3.
96
Temporary error occurred in RTD card
located in slot X130.
106
Measurement error in RTD card located
in slot X130.