ABB RED615 Technical Manual page 870

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 13
IED physical connections
864
GUID-FDC31D60-8F9F-4D2A-A1A2-F0E57553C06B V1 EN
Figure 467:
Jumper connectors on communication module
Table 684:
2-wire EIA-485 jumper connectors
Group
Jumper connection
1-2
X3
2-3
1-2
X5
2-3
1-2
X6
2-3
1-2
X7
2-3
1-2
X8
2-3
1-2
X9
2-3
1 2 3
X 8
X 9
X 7
X 3
X 6
X 5
1 2 3
X 24
X 15
Description
A+ Bias enabled
A+ Bias Disabled
B- Bias enabled
B- Bias Disabled
Bus termination
enabled
Bus termination
disabled
B- Bias enabled
B- Bias Disabled
A+ Bias enabled
A+ Bias Disabled
Bus termination
enabled
Bus termination
disabled
1YHT530004D05 D
Notes
COM1
2-wire connection
COM2
2-wire connection
615 series
Technical Manual