1YHT530004D05 D
615 series
Technical Manual
Name
Type
BLK_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
Table 590:
ESXSWI Input signals
Name
Type
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
Table 591:
CBXCBR Output signals
Name
Type
SELECTED
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
OPEN_ENAD
BOOLEAN
CLOSE_ENAD
BOOLEAN
Table 592:
DCXSWI Output signals
Name
Type
SELECTED
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
Table continues on next page
Default
Description
0=False
Blocks closing
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
0=False
Executes the command for open direction
0=False
Executes the command for close direction
0=False
Apparatus open position
0=False
Apparatus closed position
Default
Description
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
0=False
Executes the command for open direction
0=False
Executes the command for close direction
0=False
Apparatus open position
0=False
Apparatus closed position
Description
Object selected
Executes the command for open direction
Executes the command for close direction
Apparatus open position
Apparatus closed position
Apparatus position is ok
Opening is enabled based on the input status
Closing is enabled based on the input status
Description
Object selected
Executes the command for open direction
Executes the command for close direction
Apparatus open position
Apparatus closed position