Frequency
[Hz]
50 Hz
49 Hz
ST_FRG
Start of operation timer
OPR_FRG
OPERATE
GUID-DB333B09-D987-4A62-ABAE-7B70ACA275EB V2 EN
Figure 265:
Load-shedding operation in the "Freq< AND df/dt>" mode when
only the df/dt condition is satisfied (Rated frequency=50 Hz)
Restore detection
If after the activation of the OPERATE input the frequency recovers to a level
above the Restore start Val setting, the RESTORE signal output is activated. The
RESTORE output remains active for a 100 ms. The Restore mode setting is used to
select the restoring mode to be "Disabled", "Auto" or "Manual".
Start value Freq set at 0.975 xFn
Start value df/dt set at -0.020 xFn/s
Operate Tm df/dt = 500ms
Operate Tm Freq = 1000ms
Load shed mode = Freq< AND df/dt
1s
500ms
OPERATE is not
activated in this case
as Freq< condition not
satisfied
Section 4
Protection functions
Time [s]
507