Iocos(φ) criterion selected, reverse-type fault
=> FAULT_DIR = 2
GUID-54ACB854-F11D-4AF2-8BDB-69E5F6C13EF1 V2 EN
Figure 145:
Operating characteristic Iocos(φ) in reverse fault
Phase angle 80
The operation criterion phase angle 80 is selected with the Operation mode setting
by using the value "Phase angle 80".
Phase angle 80 implements the same functionality as the phase angle but with the
following differences:
•
The Max forward angle and Max reverse angle settings cannot be set but they
have a fixed value of 80 degrees
•
The sector limits of the fixed sectors are rounded.
The sector rounding is used for cancelling the CT measurement errors at low
current amplitudes. When the current amplitude falls below three percent of the
nominal current, the sector is reduced to 70 degrees at the fixed sector side. This
makes the protection more selective, which means that the phase angle
measurement errors do not cause faulty operation.
There is no sector rounding on the other side of the sector.