Emc Installation Requirements; Installation In Hazardous Areas - GE PROFINET PACSystems RX3i Quick Start Manual

Controller module
Hide thumbs Also See for PROFINET PACSystems RX3i:
Table of Contents

Advertisement

IC695PNC001-AJ PROFINET Controller Module
References
For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support
website,
http://support.ge-ip.com.
GFK-2571, PACSystems RX3i PROFINET Controller Manual
GFK-2572, PACSystems RX3i PROFINET Controller Command Line Interface Manual
GFK-2721, VersaMax PROFINET Scanner User's Manual
GFK-2314, PACSystems RX3i System Manual
GFK-2222, PACSystems CPU Reference Manual

EMC Installation Requirements

To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the IC695PNC001 module is used
shall be mounted in a metal enclosure when three or more IC695PNC001 modules are used. All surfaces of the
enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity. Wiring external to the
enclosure must be routed in metal conduit or the equivalent. The conduit must be mounted to the enclosure using
standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit.
When installing, operating, or maintaining the IC695PNC001, personnel must insure any electrostatic charge is
discharged through the use of a grounded ESD strap or other means.
General Conditions of Safe Use
This product is intended for use with the RX3i system. Its components are considered open equipment (having live
electrical parts that may be accessible to users) and must be installed in an ultimate enclosure that is manufactured to
provide safety. As a minimum, the enclosure shall provide a degree of protection against solid objects as small as
12mm (e.g. fingers). This equates to a NEMA/UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a
pollution degree 2 environment. For details about installing RX3i rack systems, refer to GFK-2314.
If you need technical help, contact Technical Support. For phone numbers and email addresses, see the back cover of
this Guide.

Installation in Hazardous Areas

The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive
atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
• This equipment is an open-type device and is meant to be installed in an enclosure suitable for the environment that
is only accessible with the use of a tool.
• Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or nonhazardous locations only.
Warning – EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2.
Warning – WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES;
AND
Warning – DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE
AREA IS KNOWN TO BE NONHAZARDOUS.
Warning – EXPLOSION HAZARD - USB PORT IS ONLY FOR USE IN NONHAZARDOUS LOCATIONS, DO NOT USE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
ATEX Zone 2
This product must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC and
rated IP54. The enclosure shall only be able to be opened with the use of a tool
3
GFK-2573K