5. PARAMETERS
No.
Symbol
PL09
LPWM
Magnetic pole detection voltage level
This is used to set a direct current exciting voltage level during the magnetic pole detection.
If [AL. 32 Overcurrent], [AL. 50 Overload 1], or [AL. 51 Overload 2] occurs during the magnetic
pole detection, decrease the setting value.
If [AL. 27 Initial magnetic pole detection error] occurs during the magnetic pole detection,
increase the setting value.
PL17
LTSTS
Magnetic pole detection - Minute position detection method - Function selection
To enable the parameter, select "Minute position detection method (_ _ _ 4)" in [Pr. PL08].
Setting
digit
_ _ _ x
_ _ x _
_ x _ _
x _ _ _
Table 5.9 Response of minute position detection method at magnetic
Setting value
Table 5.10 Load to motor mass ratio/load to motor inertia ratio
Setting value
PL18
IDLV
Magnetic pole detection - Minute position detection method - Identification signal amplitude
Set an identification signal amplitude used in the minute position detection method.
This parameter is enabled only when the magnetic pole detection is the minute position
detection method.
However, setting "0" will be 100% amplitude.
Name and function
Response selection
Set a response of the minute position detection method.
When reducing a travel distance at the magnetic pole detection,
increase the setting value. Refer to table 5.9 for settings.
Load to motor mass ratio/load to motor inertia ratio selection
Select a load to mass of the linear servo motor primary-side ratio or
load to mass of the direct drive motor inertia ratio used at the
minute position detection method. Set a closest value to the actual
load.
Refer to table 5.10 for settings.
For manufacturer setting
pole detection
Response
0
Low response
1
2
3
4
5
6
7
Middle response
Load to motor mass
ratio/load to motor
inertia ratio
0
10 times or less
1
10 times
2
20 times
3
30 times
4
40 times
5
50 times
6
60 times
7
70 times
Explanation
Setting value
Response
8
Middle response
9
A
B
C
D
E
F
High response
Load to motor mass
Setting value
ratio/load to motor
inertia ratio
8
80 times
9
90 times
A
100 times
B
110 times
C
120 times
D
130 times
E
140 times
F
150 times or more
5 - 50
Initial
Setting
value
range
[unit]
30
0 to 100
[%]
Refer to Name
and function
column.
Initial
value
0h
0h
0h
0h
0
0 to 100
[%]