4. STARTUP
c) When you use a brake unit and power regeneration converter for 5 kW or more servo
amplifiers
For 5 kW or 7 kW servo amplifiers, the lead wire of the built-in regenerative resistor
connected to P+ terminal and C terminal should not be connected.
Brake unit, power regeneration converter should be connected to P+ terminal and N-
terminal. (Refer to section 11.3 to 11.4.)
A twisted cable should be used when wiring is over 5 m and under 10 m using a brake unit.
(Refer to section 11.3)
d) When you use a power regeneration common converter for 11 kW or more servo amplifiers
Power regeneration common converter should be connected to P4 terminal and N- terminal.
(Refer to section 11.5.)
e) The power factor improving DC reactor should be connected between P3 and P4. (Refer to
section 11.11.)
3) 100 V class
The lead wire between P+ terminal and D terminal should not be connected.
The regenerative option should be connected to P+ terminal and C terminal.
A twisted cable should be used. (Refer to section 11.2.4.)
(2) I/O signal wiring
(a) The I/O signals should be connected correctly.
Use DO forced output to forcibly turn on/off the pins of the CN3 connector. This function can be used
to perform a wiring check. In this case, switch on the control circuit power supply only.
Refer to section 3.2 for details of I/O signal connection.
(b) 24 V DC or higher voltage is not applied to the pins of the CN3 connector.
(c) SD and DOCOM of the CN3 connector is not shorted.
Servo amplifier
Power factor improving
DC reactor
P3
(Note)
P4
Note. Always disconnect between P3 and P4.
Servo amplifier
CN3
DOCOM
SD
4 - 5