Digital Input Function: Remote Alarm; Digital Input Function: Remote Trip - GE 469 Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4.4 S3 DIGITAL INPUTS
Once the Remote Alarm function is chosen for one of the assignable digital inputs, the setpoint messages
shown here will follow the assignment message. An alarm relay may be selected and the name of the alarm
may be altered. A contact closure on the digital input assigned as Remote Alarm will cause an alarm within 100
ms with the name that has been chosen. Multiple sources may be used to trigger a remote alarm by paralleling
inputs.
4
Once the Remote Trip function is chosen for one of the assignable digital inputs, the setpoint messages shown
here will follow the assignment message. A trip relay may be selected and the name of the trip may be altered.
A contact closure on the digital input assigned as Remote Trip will cause a trip within 100 ms with the name
that has been chosen. Multiple sources may be used to trigger a remote trip by paralleling inputs.
4-18
REMOTE ALARM NAME:
ESCAPE
Remote Alarm
MESSAGE
REMOTE
ESCAPE
ALARM: Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
REMOTE ALARM
ESCAPE
EVENTS: Off
MESSAGE
REMOTE
PUSH-BUTTO N
469 Digital Input
Figure 4–5: REMOTE ALARM FROM MULTIPLE SOURCES
REMOTE TRIP NAME:
ESCAPE
Remote Trip
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
REMOTE
PUSH-BUTTO N
469 Digital Input
Figure 4–6: REMOTE TRIP FROM MULTIPLE SOURCES
469 Motor Management Relay
4 SETPOINT PROGRAMMING

4.4.8 DIGITAL INPUT FUNCTION: REMOTE ALARM

Range: 20 character alphanumeric
Range: Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2
Range: On, Off
Dry contact from other device

4.4.9 DIGITAL INPUT FUNCTION: REMOTE TRIP

Range: 20 character alphanumeric
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
Dry contact from other device