Error Code Description
1025 CC46 Description: Loss of pgood on an I/O planar in the I/O drawer at location U2.19
Action:This error code can be caused by hot-plugging RIO cables. To see if this is a recoverable
error, do the following:
1. Power down the system by following the appropriate procedure in "Powering Off and Powering
On the System" on page 854.
2. After the system is shut down, 350V dc must be removed from the DCAs in the I/O drawer that
reported the error:
v If a High Performance Switch (7045-SW4) is installed in the CEC frame, follow the
instructions in "Powering Off and Powering On the System" on page 854 for deactivating a
system's I/O drawer after the system is shut down.
v If a High Performance Switch (7045-SW4) is not present in the CEC frame, use the UEPO
switch to remove 350V dc from all of the drawers in the frame.
3. Then boot the system by following the appropriate procedure in "Powering Off and Powering On
the System" on page 854. At any point after the service processor comes up to standby,
indicated by OK in the operator panel in the media drawer, look at the service action event log
in Service Focal Point on the HMC. If this error code does not reoccur, no action is required. If
this error code reoccurs, replace the I/O planar, location: U2.19-P2.
1025 CD96 A power short has been detected in the DASD
subsystem in an I/O drawer.
1025 CDA6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1025 CDB6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1025 CDC6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1025 F4x6 Hardware configuration does not support
N-mode power.
1025 F516 An N+1 boundary (DCA or fan) has dropped to
N-mode status in fourth I/O subsystem in second
rack (I/O subsystem 8), location: U2.19.
1025 F526 An N+1 boundary (DCA or fan) has dropped to
N-mode status in fourth I/O subsystem in second
rack (I/O subsystem 8), location: U2.19.
1025 xx11 Fourth I/O subsystem in second rack (I/O
subsystem 8), DCA-1
1025 xx13 Seeprom fault on DCA-1 in fourth I/O subsystem
in second rack (I/O subsystem 8)
Action/
Possible Failing FRU
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Call Service Support
This is normally an informational message. It
should be accompanied by other error codes that
more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
This is normally an informational message. It
should be accompanied by other error codes that
more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
U2.19-V1
U2.19-V1
Chapter 5. Error Code to FRU Index
487