IBM pSeries 690 Service Manual page 450

Hide thumbs Also See for pSeries 690:
Table of Contents

Advertisement

Error Code Description
1015 F516 An N+1 boundary (DCA or fan) has dropped to
N-mode status in the second I/O subsystem,
location: U1.5.
1015 F526 An N+1 boundary (DCA or fan) has dropped to
N-mode status in the second I/O subsystem,
location: U1.5.
1015 xx11 Second I/O subsystem in primary rack, DCA-1
1015 xx13 Seeprom fault on DCA-1 in second I/O
subsystem in primary rack
1015 xx15 Second I/O subsystem in primary rack, DCA-1,
cable fault
1015 xx17 Problem with fan 1 and fan 3 in second I/O
subsystem in primary rack
1015 xx21 Second I/O subsystem in primary rack, DCA-2
1015 xx23 Seeprom fault on DCA-2 in second I/O
subsystem in primary rack
1015 xx25 Second I/O subsystem in primary rack, DCA-2,
cable fault
1015 xx27 Problem with fan 2 and fan 4 in second I/O
subsystem in primary rack
1015 xx31 Second I/O subsystem in primary rack, I/O
subsystem backplane 1 fault
1015 xx33 Seeprom fault on I/O subsystem backplane 1 in
second I/O subsystem in primary rack
1015 xx41 Second I/O subsystem in primary rack, I/O
subsystem backplane 2 fault
434
Eserver pSeries 690 Service Guide
Action/
Possible Failing FRU
This is normally an informational message. It
should be accompanied by other error codes that
more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
This is normally an informational message. It
should be accompanied by other error codes that
more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
U1.5-V1
U1.5-V1
Go to "MAP 1520: Power" on page 194 with
these pairs of location codes:
1. U1.5-V1/Q1 and U1.35-P2-X3/Q3
2. U1.5-V1/Q2 and U1.35-P1-X3/Q3
1. DCA-1
Location U1.5–V1
2. Fan 1,
Location U1.5–F1
3. Fan 3,
Location U1.5–F3
U1.5-V2
U1.5-V2
Go to "MAP 1520: Power" on page 194 with
these pairs of location codes:
1. U1.5-V2/Q1 and U1.35-P2-X3/Q4
2. U1.5-V2/Q2 and U1.35-P1-X3/Q4
1. DCA-2
Location U1.5–V2
2. Fan 2,
Location U1.5–F2
3. Fan 4,
Location U1.5–F4
U1.5-P1
U1.5-P1
U1.5-P2

Advertisement

Table of Contents
loading

Table of Contents