Acoustical Noise Emissions

Product Configuration
7040 Acoustical Doors
7040 Slimline Doors
Notes:
1. Noise levels cited are for a typical configuration (A-Frame: Bulk Power, CEC cage, battery option, media drawer,
and two I/O drawers).
2. The 0.6-B (6-dB) reduction in noise emission levels with the acoustical rear door corresponds to a factor of 4
reduction. That is, the noise level of a single A-Frame with thin covers is about the same as the noise level of
four A-Frames with acoustical covers.
3. L
is the upper-limit A-weighted sound power level; LpAm is the mean A-weighted sound pressure level at the
WAd
1-meter bystander positions; 1 B = 10 dB.
4. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

Environmental Specifications

Environmental Specification
Temperature
Relative Humidity
(Noncondensing)
Maximum Wet Bulb
Notes:
1. Storage and shipping specifications are valid for a maximum duration of two weeks each.
2. The upper limit of the dry bulb temperature must be derated 1 degree C per 189 m (619 ft.) above 1295 m (4250
ft.). Maximum altitude for 1.1 GHz modules is 3048 m (10,000 ft.) and for 1.3 GHz modules is 2134 m (7000 ft)
Weight Distribution
The following table shows dimensions and weights used to calculate floor loading for the Eserver pSeries
690. All floor-loading calculations are intended for a raised-floor environment.
1 Frame with
Slimming Covers
Weight
Width
Depth
138
Eserver pSeries 690 Service Guide
Declared A-Weighted Sound Power
Level, L
Operating
7.5
7.9
Operating
10 to 32°C
(50 to 90°F)
Max. of 24 ° C
(75.2 ° F) with
4mm tape or DVD
RAM in rear
positions of the
Media Subsystem
8 to 80 %
23°C (73°F)
2 Frames with
Slimming Covers
1170 kg (2580 lbs.)
1973 kg (4349 lbs.)
750 mm (29.5 in.)
1539 mm (60.6 in.)
1173 mm (46.2 in.)
1173 mm (46.2 in.)
Acoustical Characteristic
Declared A-Weighted Sound Pressure
(B)
WAd
Idle
7.5
7.9
Non-Operating
10 to 43°C
(50 to 109°F)
(34 to 140°F)
8 to 80 %
27°C (73°F)
1 Frame with
Acoustical Covers
1184 kg (2610 lbs.)
750 mm (29.5 in.)
1173 mm (46.2 in.)
Level, LpAm (dB)
Operating
Idle
57
57
62
62
Storage
Shipping
1 to 60°C
–40 to 60°C
(–40 to 140°F)
5 to 80 %
5 to 100 %
29°C (84°F)
29°C (84°F)
2 Frames with
Acoustical Covers
2000 kg (4409 lbs.)