Error Code Description
1015 CC36 Description: Loss of pgood on an I/O planar in the I/O drawer at location U1.5
Action: This error code can be caused by hot-plugging RIO cables. To see if this is a recoverable
error, do the following:
1.
Power down the system by following the appropriate procedure in "Powering Off and Powering
On the System" on page 854.
2.
After the system is shut down, 350V dc must be removed from the DCAs in the I/O drawer that
reported the error:
v If a High Performance Switch (7045-SW4) is installed in the CEC frame, follow the
instructions in "Powering Off and Powering On the System" on page 854 for deactivating a
system's I/O drawer after the system is shut down.
v If a High Performance Switch (7045-SW4) is not present in the CEC frame, use the UEPO
switch to remove 350V dc from all of the drawers in the frame.
3. Then boot the system by following the appropriate procedure in "Powering Off and Powering On
the System" on page 854. At any point after the service processor comes up to standby,
indicated by OK in the operator panel in the media drawer, look at the service action event log
in Service Focal Point on the HMC. If this error code does not reoccur, no action is required. If
this error code reoccurs, replace the I/O planar, location: U1.5-P1.
1015 CC46 Description: Loss of pgood on an I/O planar in the I/O drawer at location U1.5
Action:This error code can be caused by hot-plugging RIO cables. To see if this is a recoverable
error, do the following:
1. Power down the system by following the appropriate procedure in "Powering Off and Powering
On the System" on page 854.
2. After the system is shut down, 350V dc must be removed from the DCAs in the I/O drawer that
reported the error:
v If a High Performance Switch (7045-SW4) is installed in the CEC frame, follow the
instructions in "Powering Off and Powering On the System" on page 854 for deactivating a
system's I/O drawer after the system is shut down.
v If a High Performance Switch (7045-SW4) is not present in the CEC frame, use the UEPO
switch to remove 350V dc from all of the drawers in the frame.
3. Then boot the system by following the appropriate procedure in "Powering Off and Powering On
the System" on page 854. At any point after the service processor comes up to standby,
indicated by OK in the operator panel in the media drawer, look at the service action event log
in Service Focal Point on the HMC. If this error code does not reoccur, no action is required. If
this error code reoccurs, replace the I/O planar, location: U1.5-P2.
1015 CD96 A power short has been detected in the DASD
subsystem in an I/O drawer.
1015 CDA6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1015 CDB6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1015 CDC6 A power short has been detected in the DASD
subsystem in an I/O drawer.
1015 F4x6 Hardware configuration does not support
N-mode power.
Action/
Possible Failing FRU
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Go to "MAP 1520: Power" on page 194.
Call Service Support