Assume the notch frequency is f
parameters can be calculated as follows:
p1663=p1665=f
p1664=f
p1666=(f
9.7

Low frequency vibration suppression

Low frequency vibration suppression function is position setpoint filter function. It can
suppression the vibration between 0.5 Hz to 62.5 Hz. The function is available in IPos control
mode.
Related parameters
When you use the vibration suppression function, you need to configure the following
parameters accordingly:
Parame-
Value
Default
ter
range
value
p29035
0 to 1
0
p31581
0 to 1
0
p31585
0.5 to 62.5 1
p31586
0 to 0.99
0.03
Operating steps
Step
Description
Set the drive to servo off status.
Select the filter type by p31581.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Default
Unit
Description
value
1000
Hz
Natural frequency of current notch filter 4 denominator.
0.3
-
Damp of current notch filter 4 denominator.
1000
Hz
Natural frequency of current notch filter 4 numerator.
0.01
-
Damp of current notch filter 4 numerator.
sp
/ (2 × f
)
BB
sp
× 10
)/ (2 × f
)
(k/20)
BB
sp
Unit
Description
-
Vibration suppression activation.
0: disble
1: enable
-
Vibration suppression filter type.
0: filter type rugged
1: filter type sensitive
Hz
Vibration suppression filter frequency.
-
Vibration suppression filter damp.
9.7 Low frequency vibration suppression
, notch width is f
, and notch depth is K, then the filter
sp
BB
Comment
Vibration suppression filter type.
0: filter type rugged
1: filter type sensitive
Tuning
263

Hide quick links:

Advertisement

Table of Contents
loading