7.3
Pulse train input position control (PTI)
7.3.1
Sequence of SON
When the SINAMICS V90 servo drive operates in pulse train input position control mode
(PTI), the pulse train setpoint must be send out after the RDY signal is ok.
Timing diagram
7.3.2
Selecting a setpoint pulse train input channel
As mentioned before, the SINAMICS V90 servo drive supports two channels for the setpoint
pulse train input:
● 24 V single end pulse train input
● High-speed 5 V differential pulse train input (RS485)
You can select one of these two channels by setting the parameter p29014:
The position pulse train inputs come from either of the following two terminal groups:
● PTIA_D+, PTIA_D-, PTIB_D+, PTIB_D-
● PTIA_24P, PTIA_24M, PTIB_24P, PTIB_24M
For more information about wiring, refer to Section "Control/Status interface (Page 90)" and
"PTIs (Page 100)".
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Parameter
Value
p29014
0
1
7.3 Pulse train input position control (PTI)
Setpoint pulse train input channel
High-speed 5 V differential pulse train input
(RS485)
24 V single end pulse train input
Control functions
Default
✓
171