If the dynamic factor setting cannot be increased up to the desired level because of machine
resonance beyond 250 Hz, the function of resonance suppression can be used to suppress
machine resonance and thus increase dynamic factor. Refer to Section "Resonance
suppression (Page 260)" for detailed information about the function of resonance
suppression.
Note
The tuning configuration parameters must be set carefully when the auto tuning function is
disabled (p29021=0).
After servo on, the motor will run with the test signal.
When the one-button auto tuning process completes successfully, the parameter p29021 will
be set to 0 automatically. You can also set the parameter p29021 to 0 before servo on to
interrupt the one-button tuning process. Before you save the parameters on the drive, make
sure that p29021 has changed to 0.
Note
Do not use the JOG function when you use the one-button tuning function.
Note
After the one-button tuning is activated, no operation will be allowed except the servo off and
emergency stop.
With one-button auto tuning, the servo drive can automatically estimate the ratio of load
moment of inertia and set the following relevant parameters accordingly.
Parame-
ter
p1414
p1415
p1417
p1418
p1419
p1420
p1441
p1656
p1658
p1659
p2533
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Dynamic factor (p29020)
19
...
35
Value range
Defult
value
0 to 3
0
0 to 2
0
0.5 to 16000
1999
0.001 to 10
0.7
0.5 to 16000
1999
0.001 to 10
0.7
0 to 50
0
0 to 15
1
0.5 to 16000
1999
0.001 to 10
0.7
0 to 1000
0
Unit
Description
-
Speed setpoint filter activation
-
Speed setpoint filter 1 type
Hz
Speed setpoint filter 1 denominator natural frequency
-
Speed setpoint filter 1 denominator damping
Hz
Speed setpoint filter 1 numerator natural frequency
-
Speed setpoint filter 1 numerator damping
ms
Actual speed smoothing time
-
Activates current setpoint filter
Hz
Current setpoint filter 1 denominator natural frequen-
cy
-
Current setpoint filter 1 denominator damping
ms
LR position setpoint filter time constant
9.3 One-button auto tuning
Machine rigidity
High
Tuning
253