Diagnostics
11.2 List of faults and alarms
Alarm
A30031: Hardware current
limiting in phase U
A31411: Absolute encoder
signals internal alarms
A31412: Error bit set in the
serial protocol
A52900: Failure during data
copying
A52901: Braking resistor
reaches alarm threshold
A52902: Emergency missing
A52932: PTO max limit
334
Cause
Hardware current limit for phase U re-
sponded. The pulsing in this phase is in-
hibited for one pulse period.
Closed-loop control is incorrectly pa-
rameterized.
Fault in the motor or in the power ca-
bles.
The power cables exceed the maxi-
mum permissible length.
Motor load too high.
Power unit defective.
Note:
Alarm A30031 is always output if, for a
Power Module, the hardware current limit-
ing of phase U, V or W responds.
The absolute encoder fault word includes
alarm bits that have been set.
The encoder sends a set error bit via the
serial protocol.
Copying is halted.
The micro SD card/SD card was
plugged out.
The drive is not in the stop state.
The heat capacity reaches the threshold
(p29005) of the braking resistor capacity.
Implement servo on when the emergency
input (EMGS) is switched off.
For incremental encoder, when PTO fre-
quency exceeds 280K, drive will output
A52932 to remind that exceed limitation.
For absolute encoder, when PTO frequen-
cy exceeds 120K, drive will output A52932
to remind that exceed limitation.
Remedy
Check the motor data. As an alternative, run
a motor data identification.
Check the motor circuit configuration
(star-delta)
Check the motor load.
Check the power cable connections.
Check the power cables for short-circuit or
ground fault.
Check the length of the power cables.
Replace the encoder.
Carry out a POWER ON (power off/on) for
all components.
Check that the encoder cables are routed
in compliance with EMC.
Check the plug connections.
Replace the encoder.
Re-plug in the micro SD card/SD card.
Make sure the drive is in the stop state.
Change the external braking resistor.
Increase deceleration time.
Switch on the emergency input (EMGS) and
then implement servo on.
Change PTO ratio.
SINAMICS V90, SIMOTICS S-1FL6