Siemens SINAMICS V90 Operating Instructions Manual page 213

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

FC16 - Write multiple registers
When a message with FC = 0x10 is received, then 5 + N bytes of data are expected, that is,
FC16 has 5 + N bytes of data:
● Two bytes for the starting address
● Two bytes for the number of registers
● One byte for the byte count
● N bytes for the register values
Byte 1
Byte 2
Byte 3
Address
FC
Start
(0x10)
address
(most
signifi-
cant
byte)
Operating steps
Description
Configure the RS485 bus address by parameter
p29004.
Select the communication protocol by parameter
p29007.
Select the command and setpoint source by parame-
ter p29008.
Set the transmission baud rate by parameter p29009.
Set control mode for the drive by p29003.
Save the parameters and restart the drive.
Configure the PLC parameters.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Byte 4
Byte 5
Byte 6
Start
Number
Number
address
of regis-
of regis-
(least
ters
ters
signifi-
(most
(least
cant
signifi-
signifi-
byte)
cant
cant
byte)
byte)
You can configure the slaver address from 1 to 31.
Note:
Keep the PLC baud rate the same as the drive setting.
Set even parity check for the PLC.
7.7 Communicating with the PLC
Byte 7
Byte 7 +
n
Number
nth
of bytes
value
(most
signifi-
cant
byte)
Comment
p29007 = 0: No protocol
p29007 = 1: USS protocol
p29007 = 2: Modbus protocol
p29008 = 1: Setpoint and control word from Modbus PZD
p29008 = 2: No control word.
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Control functions
Byte 8 +
Byte 9 +
Byte 10 +
n
n
n
nth
CRC
CRC
value
(least
signifi-
cant
byte)
213

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents