The following diagram shows how the internal torque limit functions:
External torque limit
Parameter settings:
Parameter Value range
p29041[1]
0 to 300
p29041[1] is the scaling of analog input 2.
For example, if p29041[1] is 100%, the relationship between torque limit value and analog
input is shown as follows:
In this case, analog input of 5 V corresponds to 50% of rated torque and 10 V corresponds to
100% of rated torque.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Default
Unit
300
%
Analog torque limit scaling (value
corresponding to 10V)
7.3 Pulse train input position control (PTI)
Description
Control functions
Digital input
TLIM1
TLIM2
0
1
181