Diagnostics
11.2 List of faults and alarms
Fault
F30001: Power unit: Overcur-
rent
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30002: DC link voltage,
overvoltage
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30003: DC link voltage,
undervoltage
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30004: Drive heat sink over-
temperature
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30005: Power unit: Overload
I
t
2
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
326
Cause
The power unit has detected an overcur-
rent condition.
Closed-loop control is incorrectly pa-
rameterized.
Controller parameters are not proper.
Motor has a short-circuit or fault to
ground (frame).
Power cables are not correctly con-
nected.
Power cables exceed the maximum
permissible length.
Power unit defective.
Line phase interrupted.
The power unit has detected overvoltage
in the DC link.
Motor regenerates too much energy.
Device connection voltage too high.
Line phase interrupted.
The power unit has detected an undervolt-
age condition in the DC link.
Line supply failure
Line supply voltage below the permis-
sible value.
Line supply infeed failed or interrupted.
Line phase interrupted.
The temperature of the power unit heat
sink has exceeded the permissible limit
value.
Insufficient cooling, fan failure.
Overload.
Surrounding temperature too high.
Pulse frequency too high.
The power unit was overloaded.
The permissible rated power unit cur-
rent was exceeded for an inadmissibly
long time.
The permissible load duty cycle was
not maintained.
Remedy
Check the motor data - if required, carry
out commissioning.
Modify speed loop Kp (p29120), position
loop Kv (p29110).
Check the motor circuit configuration
(star-delta).
Check the power cable connections.
Check the power cables for short-circuit or
ground fault.
Check the length of the power cables.
Replace power unit.
Check the line supply phases.
Check the external braking resistor con-
nection.
Increase the ramp-down time.
Activate the DC link voltage controller.
Use a braking resistor.
Increase the current limit of the infeed or
use a larger module.
Check the device supply voltage.
Check the line supply phases.
Check the line supply voltage
Check the line supply infeed and observe
the fault messages relating to it (if there
are any)
Check the line supply phases.
Check the line supply voltage setting.
Check whether the fan is running.
Check the fan elements.
Check whether the surrounding tempera-
ture is in the permissible range.
Check the motor load.
Reduce the pulse frequency if this is high-
er than the rated pulse frequency.
Reduce the continuous load.
Adapt the load duty cycle.
Check the motor and power unit rated
currents.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884