Rack Requirements

You can mount the device on two-post racks or four-post racks.
Rack requirements consist of:
Rack type
Mounting bracket hole spacing
Guidelines
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the
device can be mounted in any rack that provides holes spaced at that distance.
Ensure that the rack complies with the standards for a 19-in. rack as defined in Cabinets,
Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the
Electronics Industry Association.
Ensure that the rack rails are spaced widely enough to accommodate the device chassis'
external dimensions. The outer edges of the front-mounting brackets extend the width
to 19 in. (48.26 cm).
The front and rear rack rails must be spaced between 28 in. (71.1 cm) and 36 in. (91.4
cm) front-to-back.
The rack must be strong enough to support the weight of the device.
Ensure that the spacing of rails and adjacent racks allows for proper clearance around
the device and rack.
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum
stability.