Page 2
FROM/TO instructions in DVP Slim series MPU program, the data in the module can be read and written. There are many 16-bit control registers (CR) in DVP04TC-S. The power unit is separate from it and is small in size and easy to install.
Page 3
Note2: Terminal SLD is a grounding location for noise suppression. Note3: Please connect power supply module terminal and DVP04TC-S temperature measurement module terminal to system earth ground. Warning1: Do NOT wire empty terminals. Warning2: Only use copper conducting wires with a temperature rating of 60/75°C and the length must be less than 50 m.
Page 4
Control Register Address Save Register content Description Set up by the system: H’4096 Model name DVP04TC-S model code=H’8B b15~b12 b11~b9 b8~b6 b5~b3 b2~b0 Reserved Example: Setting of CH1 (b2, b1, b0) set to (0, 0, 0), use J-type. (b2, b1, b0) set to (0, 0, 1), use K-type.
Page 5
H’40AE CH1 OFFSET Value Adjust offset value of channels CH1 ~ CH4. H’40AF CH2 OFFSET Value The range is -1,000 ~ +1,000 and default setting is K0. H’40B0 CH3 OFFSET Value (Unit: 0.1°C). H’40B1 CH4 OFFSET Value Set H'5678 to enable PID mode, other set H’40B3 PID mode setting values are invalid.
Page 6
Note: Each error code will have corresponding bit (b0 ~ b7). Two or more errors may happen at the same time. 0 means normal and 1 means having error. 6. When CR#29 is set to H’5678, CR#0 ~ CR#34 can be used for PID settings in DVP04TC-S V3.08 and versions above.