Specifications; General Specifications; Emc Standards; Emi - Delta AH500 Manual

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

AH 5 00 Mo d u le Ma n ua l

1.2 Specifications

1.2.1

General Specifications

Item
Operating
temperature
Storage temperature
Operating humidity
Storage humidity
Vibration/Shock
resistance
Work environment
Installation location
Pollution degree
1.2.2

EMC Standards

1.2.2.1 EMI

Port
Enclosure port
(radiated)
(measured at a
distance of 10
meters)
AC power port
(conducted)

1.2.2.2 EMS

Environmental
phenomenon
Electrostatic
discharge
Radio frequency
electromagnetic
field
Amplitude
modulated
Power frequency
magnetic field
1 - 4
-20~60°C
-40~70°C
5~95%
No condensation
5~95%
No condensation
International standards IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2
& IEC 68-2-27 (TEST Ea)
No corrosive gas exists.
In a control box
2
Frequency range
30-230 MHz
230-1000 MHz
0.15-0.5 MHz
0.5-30 MHz
Reference standard
IEC 61000-4-2
80% AM,
IEC 61000-4-3
1 kHz
sinusoidal
IEC 61000-4-8
Specifications
Level (Normative)
40 dB (μV/m) quasi-peak
47 dB (μV/m) quasi-peak
79 dB (μV) quasi-peak
66 dB (μV) average
73 dB (μV) quasi-peak
60 dB (μV) average
Test
Contact
Air
2.0-2.7 GHz
1.4-2.0 GHz
80-1000 MHz
60 Hz
50 Hz
Reference standard
IEC 61000-6-4
IEC 61000-6-4
Test level
±4 kV
±8 kV
1 V/m
3 V/m
10 V/m
30 A/m
30 A/m

Hide quick links: