Contents Of The Fieldbus Status Word (Abb Drives Profile) - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

638 Fieldbus control through a fieldbus adapter

Contents of the fieldbus Status word (ABB Drives profile)

The upper case boldface text refers to the states shown in the state diagram (page
639).
Bit
Name
0
Ready to switch
ON
1
Ready run
2
Ready ref
3
Tripped
4
Off 2 inactive
5
Off 3 inactive
6
Switch-on inhibited 1
7
Warning
8
At setpoint
9
Remote
10
Above limit
11
User bit 0
12
User bit 1
13
User bit 2
14
User bit 3
15
Reserved
Value STATE/Description
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
READY TO OPERATE.
0
OFF1 ACTIVE.
1
OPERATION ENABLED.
0
OPERATION INHIBITED. See parameters
word
and
06.25 Drive inhibit status word 2
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
SWITCH-ON INHIBITED.
0
1
Warning active.
0
No warning active.
1
OPERATING. Actual value equals reference = is within tolerance
limits (see parameters 46.21...46.23).
0
Actual value differs from reference = is outside tolerance limits.
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
-
See parameter
-
See parameter
-
See parameter
-
See parameter
-
See parameter
06.29 MSW bit 10
sel.
06.30 MSW bit 11
sel.
06.31 MSW bit 12
sel.
06.32 MSW bit 13
sel.
06.33 MSW bit 14
sel.
06.18 Start inhibit status
for the inhibiting condition.