364 Parameters
No.
Name/Value
45.19
Comparison power
0.0 ... 100000.0 kW Motor power.
45.21
Energy calculations
reset
Done
Reset
46
46 Monitoring/scaling
settings
46.01
Speed scaling
0.10 ... 30000.00
rpm
46.02
Frequency scaling
0.10 ... 1000.00 Hz
46.03
Torque scaling
0.1 ... 1000.0%
46.04
Power scaling
0.10 ... 30000.00
kW or
0.10 ... 40214.48
hp
Description
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
Resets the savings counter parameters
Reset not requested (normal operation), or reset complete.
Reset the savings counter parameters. The value reverts
automatically to Done.
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
Speed reference
ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.12 Maximum
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in fieldbus,
master/follower etc. communication.
Acceleration/deceleration terminal/initial speed.
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
Frequency reference
chain). The frequency acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.14 Maximum
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in fieldbus, master/follower etc. communication.
Acceleration/deceleration terminal/initial frequency.
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in fieldbus, master/follower etc.
communication.
See also parameter
46.42 Torque
Torque corresponding to 10000 on fieldbus.
Defines the output power value that corresponds to 10000 in
fieldbus, master/follower etc. communication. The unit is
selected by parameter
96.16 Unit
Power corresponding to 10000 on fieldbus.
45.01...45.09
23
speed).
28
frequency).
decimals.
selection.
Def/FbEq16
0.0 kW
See par.
46.04
Done
0
1
1500.00 rpm;
1800.00 rpm
(95.20
b0)
1 = 1 rpm
50.00 Hz;
60.00 Hz
(95.20
b0)
10 = 1 Hz
100.0%
10 = 1%
1000.00 kW
or hp
1 = 1 unit