Motor Thermal Protection - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

116 Program features

Motor thermal protection

The control program features two separate motor temperature monitoring functions.
The temperature data sources and warning/trip limits can be set up independently for
each function.
The motor temperature can be monitored using
• the motor thermal protection model (estimated temperature derived internally
inside the drive), or
• sensors installed in the windings. This will result in a more accurate motor model.
In addition to temperature monitoring, a protection function is available for 'Ex' motors
installed in a potentially explosive atmosphere.
Motor thermal protection model
The drive calculates the temperature of the motor on the basis of the following
assumptions:
1. When power is applied to the drive for the first time, the motor is assumed to be at
ambient temperature (defined by parameter
After this, when power is applied to the drive, the motor is assumed to be at the
estimated temperature.
2. Motor temperature is calculated using the user-adjustable motor thermal time and
motor load curve. The load curve should be adjusted in case the ambient
temperature exceeds 30 °C.
Note: The motor thermal model can be used when only one motor is connected to
the inverter.
Temperature monitoring using PTC sensors
One PTC sensor can be connected to digital input DI6.
+24VD
T
DI6
The resistance of the PTC sensor increases when its temperature rises. The
increasing resistance of the sensor decreases the voltage at the input, and eventually
its state switches from 1 to 0, indicating overtemperature.
1...3 PTC sensors can also be connected in series to an analog input and an analog
output. The analog output feeds a constant excitation current of 1.6 mA through the
sensor. The sensor resistance increases as the motor temperature rises, as does the
35.50 Motor ambient
temperature).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents