Motor Thermal Protection - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

No.
Name/Value
Other
33.64
Value counter 2
divider
0.001 ...
2147483.000
33.65
Value counter 2
warn message
Value counter 2
exceeded
Maintain motor
bearing
35
35 Motor thermal
protection
35.01
Motor estimated
temperature
-60 ... 1000
°C or °F
35.02
Measured
temperature 1
-60 ... 1000 °C,
-76 ... 1832 °F or
0...5000 ohm
35.03
Measured
temperature 2
-60 ... 1000 °C,
-76 ... 1832 °F or
0...5000 ohm
Description
Source selection (see
Terms and abbreviations
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
Divisor for value counter 2.
Selects the optional warning message for value counter 2.
A88B Value counter
2. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
A880 Motor
bearing.
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section

Motor thermal protection

Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
35.50...35.55). The unit is selected by parameter
selection
This parameter is read-only.
Estimated motor temperature.
Displays the temperature received through the source
defined by parameter
35.11 Temperature 1
selected by parameter
96.16 Unit
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Measured temperature 1.
Displays the temperature received through the source
defined by parameter
35.21 Temperature 2
is selected by parameter
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Measured temperature 2.
on page 148). -
(page 116).
source. The unit is
selection.
source. The unit
96.16 Unit
selection.
Parameters 323
Def/FbEq16
1.000
-
Value
counter 2
exceeded
5
10
-
96.16 Unit
1 = 1°
-
1 = 1 unit
-
1 = 1 unit