ABB +N5600 Firmware Instructions page 319

Single drive
Table of Contents

Advertisement

No.
Name/Value
33.35
Edge counter 1
warn message
Edge counter 1
exceeded
Counted main
contactor
Counted output
relay
Counted motor
starts
Counted power ups
Counted DC
charges
33.40
Edge counter 2
actual
0...4294967295
33.41
Edge counter 2
warn limit
0...4294967295
Description
Selects the optional warning message for signal edge counter
1.
A888 Edge counter
1. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
A884 Main
contactor.
A881 Output
relay.
A882 Motor
starts.
A883 Power
ups.
A885 DC
charge.
Displays the actual present value of signal edge counter 2.
The counter is incremented every time the signal selected by
parameter
33.43 Edge counter 2 source
either, depending on the setting of
function). A divisor may be applied to the count (see
Edge counter 2
divider).
When the counter exceeds the limit set by
counter 2 warn
limit, bit 3 of
The warning specified by
message
is also given if enabled by
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of signal edge counter 2.
Sets the warning limit for signal edge counter 2.
Warning limit for signal edge counter 2.
switches on or off (or
33.42 Edge counter 2
33.41 Edge
33.01 Counter status
33.45 Edge counter 2 warn
33.42 Edge counter 2
Parameters 319
Def/FbEq16
Edge counter
1 exceeded
2
11
12
13
14
15
-
33.44
is set to 1.
-
0
-