340 Parameters
No.
Name/Value
37.19
ULC frequency
table point 4
0.0 ... 500.0 Hz
37.20
ULC frequency
table point 5
0.0 ... 500.0 Hz
37.21
ULC underload
point 1
0.0 ... 1600.0%
37.22
ULC underload
point 2
0.0 ... 1600.0%
37.23
ULC underload
point 3
0.0 ... 1600.0%
37.24
ULC underload
point 4
0.0 ... 1600.0%
37.25
ULC underload
point 5
0.0 ... 1600.0%
37.31
ULC overload point
1
0.0 ... 1600.0%
37.32
ULC overload point
2
0.0 ... 1600.0%
37.33
ULC overload point
3
0.0 ... 1600.0%
37.34
ULC overload point
4
0.0 ... 1600.0%
37.35
ULC overload point
5
0.0 ... 1600.0%
37.41
ULC overload timer
0.0 ... 10000.0 s
37.42
ULC underload
timer
0.0 ... 10000.0 s
Description
Defines the 4th frequency point on the X-axis of the user load
curve.
Frequency.
Defines the 5th frequency point on the X-axis of the user load
curve.
Frequency.
Defines the 1st point of the underload curve.
Each point of the underload curve must have a lower value
than the corresponding overload point.
Underload point.
Defines the 2nd point of the underload curve.
Underload point.
Defines the 3rd point of the underload curve.
Underload point.
Defines the 4th point of the underload curve.
Underload point.
Defines the 5th point of the underload curve.
Underload point.
Defines the 1st point of the overload curve.
Each point of the overload curve must have a higher value
than the corresponding underload point.
Overload point.
Defines the 2nd point of the overload curve.
Overload point.
Defines the 3rd point of the overload curve.
Overload point.
Defines the 4th point of the overload curve.
Overload point.
Defines the 5th point of the overload curve.
Overload point.
Defines the time for which the monitored signal must
continuously stay above the overload curve before the drive
takes the action selected by
Overload timer.
Defines the time for which the monitored signal must
continuously stay below the underload curve before the drive
takes the action selected by
Underload timer.
37.03 ULC overload
actions.
37.04 ULC underload
actions.
Def/FbEq16
50.0 Hz
1 = 1 Hz
60.0 Hz
1 = 1 Hz
10.0%
1 = 1%
15.0%
1 = 1%
25.0%
1 = 1%
30.0%
1 = 1%
30.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
20.0 s
1 = 1 s
20.0 s
1 = 1 s