Fieldbus Adapter (Fba) - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

No.
Name/Value
49.16
Maximum ext
speed ref panel
-30000.00 ...
30000.00 rpm
49.17
Minimum ext
frequency ref panel
-500.00 ... 500.00
Hz
49.18
Maximum ext
frequency ref panel
-500.00 ... 500.00
Hz
49.24
Panel actual source
Automatic
Process PID
setpoint actual
Other
50
50 Fieldbus adapter
(FBA)
50.01
FBA A enable
Disable
Option slot 1
Option slot 2
Option slot 3
50.02
FBA A comm loss
func
No action
Description
Defines a maximum limit for control panel speed reference in
external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
24).
Maximum speed reference.
Defines a minimum limit for control panel frequency reference
in external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
24).
Minimum frequency reference.
Defines a maximum limit for control panel frequency
reference in external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
24).
Maximum frequency reference.
Selects an actual value to be displayed in the top right corner
of the control panel. This parameter is only effective when the
control panel is not an active reference source.
The active reference is displayed.
40.03 Process PID setpoint actual
Source selection (see
Terms and abbreviations
Fieldbus communication configuration.
See also chapter
Fieldbus control through a fieldbus adapter
(page 631).
Enables/disables communication between the drive and
fieldbus adapter A, and specifies the slot the adapter is
installed into.
Communication between drive and fieldbus adapter A
disabled.
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 1.
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 2.
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 3.
Selects how the drive reacts upon a fieldbus communication
break. A time delay for the action can be defined by
parameter
50.03 FBA A comm loss t
See also parameter
50.26 FBA A comm supervision
No action taken.
Parameters 373
30 Limits
are in
(page
30 Limits
are in
(page
30 Limits
are in
(page
(see page 341).
on page 148). -
out.
force.
Def/FbEq16
30000.00
rpm
See par.
46.01
-500.00 Hz
See par.
46.02
500.00 Hz
See par.
46.02
Automatic
0
1
Disable
0
1
2
3
No action
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents