No.
Name/Value
49
49 Panel port
communication
49.01
Node ID number
1...32
49.03
Baud rate
38.4 kbps
57.6 kbps
86.4 kbps
115.2 kbps
230.4 kbps
49.04
Communication
loss time
0.3 ... 3000.0 s
49.05
Communication
loss action
No action
Fault
Last speed
Speed ref safe
Description
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note: For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
Node ID.
Defines the transfer rate of the link.
38.4 kbit/s.
57.6 kbit/s.
86.4 kbit/s.
115.2 kbit/s.
230.4 kbit/s.
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
action
is taken.
Panel/PC tool communication timeout.
Selects how the drive reacts to a control panel (or PC tool)
communication break.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Refresh
settings.
See also parameters
49.07 Panel comm supervision force
and
49.08 Secondary comm. loss
No action taken.
Drive trips on
7081 Control panel
control is expected from the control panel (it is selected as
source of start/stop/reference in the currently active control
location), or if supervision is forced using parameter
Panel comm supervision
Drive generates an
A7EE Control panel loss
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the control panel, or if
supervision is forced using parameter
supervision
force.
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Drive generates an
A7EE Control panel loss
the speed to the speed defined by parameter
safe
(or
28.41 Frequency ref safe
is being used). This only occurs if control is expected from the
control panel, or if supervision is forced using parameter
49.07 Panel comm supervision
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
49.05 Communication loss
action.
loss. This only occurs if
force.
warning and
49.07 Panel comm
warning and sets
22.41 Speed ref
when frequency reference
force.
Parameters 371
Def/FbEq16
1
1 = 1
230.4 kbps
1
2
3
4
5
10.0 s
10 = 1 s
Fault
49.06
0
1
49.07
2
3