ABB +N5600 Firmware Instructions page 496

Single drive
Table of Contents

Advertisement

496 Parameters
No.
Name/Value
99.07
Motor nominal
voltage
0.0 ... 32767.0 V
99.08
Motor nominal
frequency
0.00 ... 1000.00 Hz
99.09
Motor nominal
speed
0 ... 30000 rpm
99.10
Motor nominal
power
0.00 ... 10000.00
kW or
0.00 ... 13404.83
hp
99.11
Motor nominal cos
Φ
0.00 ... 1.00
Description
Defines the nominal motor voltage supplied to the motor. This
setting must match the value on the rating plate of the motor.
Notes:
• With permanent magnet motors, the nominal voltage is the
BackEMF voltage at nominal speed of the motor. If the
voltage is given as voltage per rpm, e.g. 60 V per 1000
rpm, the voltage for a nominal speed of 3000 rpm is
3 × 60 V = 180 V.
• The stress on the motor insulation is always dependent on
the drive supply voltage. This also applies to the case
where the motor voltage rating is lower than that of the
drive and the supply.
• This parameter cannot be changed while the drive is
running.
Nominal voltage of the motor. The allowable range is 1/6...2 ×
U
(nominal voltage) of the drive. U
N
of the supply voltage range selected by parameter
Supply
voltage.
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal frequency of the motor.
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal speed of the motor.
Defines the nominal motor power. The setting must match the
value on the rating plate of the motor. If nominal power is not
shown on the rating plate, nominal torque can be entered
instead in parameter 99.12.
If multiple motors are connected to the drive, enter the total
power of the motors.
The unit is selected by parameter
Note: This parameter cannot be changed while the drive is
running.
Nominal power of the motor.
Defines the cosphi of the motor for a more accurate motor
model. The value is not obligatory, but is useful with an
asynchronous motor, especially when performing a standstill
identification run. With a permanent magnet or synchronous
reluctance motor, this value is not needed.
Notes:
• Do not enter an estimated value. If you do not know the
exact value, leave the parameter at zero.
• This parameter cannot be changed while the drive is
running.
Cosphi of the motor.
equals the upper bound
N
95.01
96.16 Unit
selection.
Def/FbEq16
0.0 V
10 = 1 V
50.00 Hz
10 = 1 Hz
0 rpm
1 = 1 rpm
0.00 kW or
hp
1 = 1 unit
0.00
100 = 1