No.
Name/Value
DIO1
DIO2
ESP CW bit 12
Other
81.19
Time trigger
0.00...650.00 hour
81.20
Number of cleaning
cycles
0...65000
81.21
First step reference
-300.00...300.00 %
81.22
First step time
0.0...6500.0 s
81.23
Off time
0.0...6500.0 s
81.24
Second step
reference
-300.00...300.00 %
81.25
Second step time
0.0...6500.0 s
81.31
Cleaning acc time
0.00...30000.00 s
81.32
Cleaning dec time
0.00...30000.00 s
81.35
Acceleration boost
current
0.00...300.00 %
Description
Digital input/output DIO1
Digital input/output DIO2
Parameter
74.01 ESP control
enable/disable status of the function.
Source selection (see
Terms and abbreviations
Defines time setting for periodic cleaning schedule.
When parameter
81.81 Since last cleaning
reaches the value set in this parameter, the cleaning request
is automatically generated.
After cleaning operation is completed, the timer is then reset
for another round with parameter
which displays remaining time till the next cleaning request
based on this parameter time setting.
Note: For the time trigger to work, parameter
cleaning option
sel, bit-2 must be set to 1.
Time trigger in hours.
Defines the desired quantity of cleaning cycles.
Each cycle consists of two speed steps with period of off-time
after each step. The period and dynamics of each cycle are
defined with parameters 81.21...81.32.
Number of cleaning cycles.
Defines speed reference for the first step of cleaning cycle.
Note that the parameter
taken into use for the cleaning operation.
First step reference in percentage.
Defines the time period for the first step of cleaning cycle.
First step time in second.
Defines the time period for the pause after each step.
The speed reference will be zero during Off time.
Off time in seconds.
Defines speed reference for the second step of cleaning
cycle.
Note that the parameter
taken into use for the cleaning operation.
Second step reference in percentage.
Defines the time period for the second step of cleaning cycle. 5.0
Second step time in seconds.
Defines acceleration time for the cleaning operation.
Cleaning acceleration time in seconds.
Defines deceleration time for the cleaning operation.
Cleaning deceleration time in seconds.
Defines the motor current reference setting used during
acceleration period of every cleaning cycle.
This helps to produce higher starting torque and assist
acceleration.
Note: For the Acceleration boost to work, parameter
Pump cleaning option
sel, bit-7 must be set to 1.
Acceleration boost current.
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
word, bit-12 status controls
on page 148). -
time counter
81.82 Until next cleaning
81.02 Pump
75.15 Starting speed
setting is also
75.15 Starting speed
setting is also
Parameters 443
Def/FbEq16
8
9
10
0.00
100 = 1hour
1
1 = 1
-10.00
10 = 1%
5.0
10 = 1s
5.0
10 = 1s
10.00
10 = 1%
10 = 1s
20.00
1 = 1s
20.00
1 = 1s
100.00
81.02