ABB +N5600 Firmware Instructions page 447

Single drive
Table of Contents

Advertisement

No.
Name/Value
NULL
AI1 scaled
AI2 scaled
FBA1 ref
FBA2 ref
EFB1 ref
EFB2 ref
Aux input data 1
Aux input data 2
Other
85.03
Input 2 source
85.04
Curve frequency 1
0.00...600.00 Hz
85.05
Curve frequency 2
0.00...600.00 Hz
85.06
Curve frequency 3
0.00...600.00 Hz
85.07
Curve frequency 4
0.00...600.00 Hz
85.08
Curve frequency 5
0.00...600.00 Hz
85.09
Pump curve scale
coef
0.000...30.000
85.10
Head at 0 flowrate 1
0.00...32000.00
85.11
Flowrate max 1
0.00...32000.00
85.12
Downthrust head 1
Description
Zero
See parameter
12.12 AI1 scaled value
See parameter
12.22 AI2 scaled value
See parameter
03.05 FB A reference 1
See parameter
03.06 FB A reference 2
See parameter
03.09 EFB reference 1
See parameter
03.10 EFB reference 2
Value set in parameter
85.71 Aux input data
Value set in parameter
85.71 Aux input data
Source selection (see
Terms and abbreviations
Defines source 2 for signal that can be used as an input for
the pump curve function.
For parameter selections, see parameter
source.
Defines Q-H pump curve frequency 1.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency in Hz.
Defines Q-H pump curve frequency 2.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency in Hz.
Defines Q-H pump curve frequency 3.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency in Hz.
Defines Q-H pump curve frequency 4.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency in Hz.
Defines Q-H pump curve frequency 5.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
Curve frequency in Hz.
Defines scale coefficient for the Q-H pump curves.
Typically, the pump manufacturers specify Q-H curves valid
for water. Set the value corresponding to a specific gravity of
the pumped fluid.
Pump curve scale coef.
Defines curve 1 maximum Head value at the corresponding
Flow value of 0.
Head at 0 flowrate 1.
Defines curve 1 maximum Flow value at the corresponding
Head value of 0.
Maximum flowrate.
Defines curve 1 Head value for the Downthrust limit.
Parameters 447
(see page 197).
(see page 199).
(page 156).
(page 156).
(page 156).
(page 156).
1.
2.
on page 148). -
85.02 Input 1
Def/FbEq16
0
1
2
3
4
5
6
7
8
Aux input
data 2
0.00
10 = 1Hz
0.00
10 = 1Hz
0.00
10 = 1Hz
0.00
10 = 1Hz
0.00
10 = 1Hz
1.000
1000 = 1
0.00
10 = 1
0.00
10 = 1
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents