ABB +N5600 Firmware Instructions page 111

Single drive
Table of Contents

Advertisement

Wiring example
The figure below shows a brake control wiring example. The brake control hardware
and wiring is to be sourced and installed by the customer.
WARNING! Make sure that the machinery into which the drive with brake
control function is integrated fulfills the personnel safety regulations. Note that
the frequency converter (a Complete Drive Module or a Basic Drive Module, as
defined in IEC 61800-2), is not considered as a safety device mentioned in the
European Machinery Directive and related harmonised standards. Thus, the
personnel safety of the complete machinery must not be based on a specific
frequency converter feature (such as the brake control function), but it has to be
implemented as defined in the application specific regulations.
The brake is controlled by bit 0 of parameter
of brake acknowledge (status supervision) is selected by parameter
acknowledge
selection. In this example,
• parameter
10.24 RO1 source
Brake control
status), and
• parameter
44.07 Brake acknowledge selection
Emergency
brake
M
Motor
44.01 Brake control
is set to
Open brake command
Brake control
hardware
115/230 VAC
Mechanical brake
Program features 111
status. The source
44.07 Brake
(ie. bit 0 of
is set to DI5.
Drive control unit
XRO1
1
NC
2
COM
3
NO
XD24
4
+24VD
XDIO
5
DI5
44.01