B.8 Message Examples
B.8 Message Examples
Below are some examples of command and response messages.
u

Reading Drive MEMOBUS/Modbus Register Contents

Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can be read out at a time.
The following table shows message examples when reading status signals, error details, data link status, and frequency
references from the slave 2 drive.
Command Message
Slave Address
Function Code
Upper
Starting No.
Lower
Upper
Data Quantity
Lower
Upper
CRC-16
Lower
u

Loopback Test

Function code 08H performs a loopback test that returns a response message with exactly the same content as the command
message. The response message can be used to check communications between the master and slave. User-defined test code
and data values can also be set.
The following table shows a message example when performing a loopback test with the slave 1 drive.
Command Message
Slave Address
Function Code
Upper
Test Code
Lower
Upper
Data
Lower
Upper
CRC-16
Lower
u

Writing to Multiple Registers

Function code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, in that the address of the first register to be written and the data quantity are set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.0 Hz for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the data
depending on the setting of H5-11.
Enter Command on page 344
326
Response Message (normal)
02H
Slave Address
03H
Function Code
00H
Data Quantity
20H
1st storage
register
00H
04H
Next storage
register
45H
F0H
Next storage
register
Next storage
register
CRC-16
01H
08H
00H
00H
A5H
37H
DAH
8DH
Refer to H5-11: Communications Enter Function Selection on page 124
for detailed descriptions.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
02H
03H
08H
Upper
00H
Lower
65H
Upper
00H
Lower
00H
Upper
00H
Lower
00H
Upper
01H
Lower
F4H
Upper
AFH
Lower
82H
Slave Address
Function Code
Test Code
Data
CRC-16
Response Message (fault)
Slave Address
Function Code
Error Code
Upper
CRC-16
Lower
Response Message
01H
08H
Upper
00H
Lower
00H
Upper
A5H
Lower
37H
Upper
DAH
Lower
8DH
02H
83H
03H
F1H
31H
and
Refer to