Chapter 3 - Start-up Information
Wizards

PID Mini-Wizard (P1.17)

The PID Mini-Wizard is activated in the Quick Setup (M1) menu. This wizard will assist with configuring the drive
for use with the PID Controller 1 in a "one-feedback/one-setpoint" mode. The control place will be I/O A and the
default process unit is %.
The following steps are required to successfully complete the PID Mini-Wizard:
Step
1
Process unit selection (P3.12.1.4)
If a process unit other than % is selected, the following questions display. Otherwise, the wizard jumps directly to
Step 5:
Step
2
Process Unit Min (P3.12.1.5)
3
Process Unit Max (P3.12.1.6)
4
Process Unit Decimals (P3.12.1.7)
5
Feedback 1 Source Selection (P3.12.3.3)
If one of the analog input signals is selected, Step 6 displays. Otherwise, the wizard jumps directly to Step 7.
Step
6
Analog Input Signal Range
7
Error Inversion (P3.12.1.8)
8
Setpoint Source Selection (P3.12.2.4)
If one of the analog input signals is selected, Step 9 displays. If the either of the options Keypad SP1 or Keypad
SP2 is selected, then Step 10 displays. Otherwise, the wizard jumps directly to Step 11.
Step
9
Analog Input Signal Range
10
Keypad SP1 (P3.12.2.1) or Keypad SP2
(P3.12.2.2)
11
Sleep Function?
If the option Yes is selected for Sleep Function, you will be prompted for the sleep function settings:
Step
Parameter/Question
12
Sleep Frequency Limit 1 (P3.13.2.7)
13
Sleep Delay 1 (P3.12.2.8)
14
Wake-up Level 1 (P3.12.2.9)
The PID Mini-Wizard is now complete.
24 | 180
Siemens Industry, Inc.
Building Technologies
Parameter/Question
Parameter/Question
Parameter/Question
Parameter/Question
Siemens BT300 HVAC Drive
Settings
Several selections, see P3.12.1.4.
Settings
Varies
Varies
Range: 0 to 4
Several selections, see P3.12.3.3.
Settings
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
Reverse Acting
Direct Acting
Several selections, see P3.12.3.4.
Settings
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
Varies
No
Yes
Settings
Varies
Varies
Varies