Siemens bt300 Operator's Manual page 159

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Code
Parameter
P5.9.3.1.1
Instance number
P5.9.3.1.2
Communication time-out 0
P5.9.3.1.3
Protocol in use
P5.9.3.1.4
BBMD OP
P5.9.3.1.5
BBMD Port
P5.9.3.1.6
Time to live
Code
Parameter
M5.9.3.2.1
Fieldbus protocol status
M5.9.3.2.2
Communication status
M5.9.3.2.3
Actual instance number
M5.9.3.2.4
Control word
M5.9.3.2.5
Status word
BACnet IP Parameter Descriptions
Ethernet Common Settings
IP address mode (P5.9.1.1)
Selectable alternatives are DHCP (Dynamic Host Configuration Protocol) and Fixed.
DHCP protocol gives IP addresses to new devices connecting to the local network. This address is valid for
a certain period of time.
A Fixed IP address is specified manually and it does not change.
When the mode is changed from DHCP to Fixed, the addresses will read:
IP: 192.168.0.10
Subnet mask: 0.0.0.0
Default gateway: 0.0.0.0
IP address (P5.9.1.3)
IP address
An
is a series of numbers, such as 192.168.0.10, which is specific to the device connected to the
Internet.
Siemens Industry, Inc.
Building Technologies
BACnet IP Settings
Table 132: Parameters Related with BACnet Used Through Ethernet.
Min
Max
0
4194304
65535
0
1
0.0.0.1
255.255.2
55.255
1
65535
0
255
Table 133: Monitoring Values.
Min
Max
1
3
0.0
99.999
0
65535
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Unit
Default
0
2406
m
0
2407
0
2408
192.168.0.1
2409
47808
2410
0
2411
Unit
Default
0.0
Serial
number
hex
hex
I/O and Hardware (M5)
ID
Description
Device object's instance number
0 = Serial number
0 = Not used
NOTE: This setting is in minutes.
0 = Not used
1 = Used
Network BBMD IP address.
BBMD UDP Port number.
ID
Description
1 = Stopped
2 = Operational
3 = Faulted
0-99 Number of messages with
errors.
0-999 Number of messages
without communication errors.
Shows actual Device Object's
instance number.
IP monitoring values.
See
IP monitoring values.
See