Connection 2
The monitoring values display the same pieces of information as for Connection 1 [➙ 155], for the 2nd and 3rd
connections.
Connection 3
The monitoring values display the same pieces of information as for Connection 1 [➙ 155], for the 2nd and 3rd
connections.
Quick Setup
For monitoring objects using ModBus TCP, complete the following steps:
If using DHCP, complete the following steps:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1).
2. Verify this is set to DHCP with AutoIP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2).
4. Verify that a valid IP Address has been assigned.
If using a Fixed IP address, complete the following:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1) > Edit.
2. Select Fixed IP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2) >
Edit.
4. Enter desired IP address.
5. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Subnet Mask
(M5.9.1.3) > Edit.
6. Enter the desired subnet mask.
7. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Default Gateway
(M5.9.1.4) > Edit.
8. Enter the desired default gateway.
Siemens Industry, Inc.
Building Technologies
NOTICE
The DHCP settings must be set properly. Otherwise, a Fixed IP address may have to
be setup.
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
157 | 180
DPD01809
2016-06-07