Chapter 4 - Parameters and Menu Structure
Parameters (M3)

Basic Settings (M3.1.1)

Structure
Parameter
P3.1.1.1
Motor Nom Voltg
P3.1.1.2
Motor Nom Freq
P3.1.1.3
Motor Nom Speed
P3.1.1.4
Motor Nom Currnt
P3.1.1.5
Motor Cos Phi
P3.1.1.6
Motor Nom Power
P3.1.1.7
Current Limit
P3.1.1.8
Motor Type

Motor Control Settings (M3.1.2)

Structure
Parameter
P3.1.2.1
Switching Freq
P3.1.2.2
Motor Switch
P3.1.2.4
Zero Freq Voltg
36 | 180
Siemens Industry, Inc.
Building Technologies
Table 14: Basic Motor Settings.
Unit
Min
V
Varies
Varies
Hz
8
320
rpm
24
19200
A
Varies
Varies
0.3
1
hp
Varies
Varies
A
Varies
Varies
IM
PMM
Table 15: Motor Control Settings.
Unit
Min
Max
kHz
1.5
Varies
No
Yes
%
0
40
Siemens BT300 HVAC Drive
Max
Default
ID
Varies
110
60
111
Varies
112
Varies
113
Varies
120
Varies
116
Varies
107
IM
650
Default
ID
Varies
601
No
653
Varies
606
Description
Defines nominal motor voltage from
Also see
motor nameplate data.
Menu Structure P1.1.
Defines nominal motor frequency
from motor nameplate data. Also
Menu Structure P1.2.
see
Defines nominal motor speed from
motor nameplate data. Also see
Menu Structure P1.3.
Defines nominal motor current from
motor nameplate data. Also see
Menu Structure P1.4.
Defines nominal motor Cos Phi
(power factor) from motor
Menu
nameplate data. Also see
Structure P1.5.
Defines nominal motor power from
motor nameplate data. Also see
Menu Structure P1.6.
Defines maximum current limit for
motor. Suggested to use Motor
Nominal Current (P3.1.1.4)
multiplied by motor service factor
from motor nameplate data. Also
Menu Structure P1.7.
see
Selection of the motor type as
follows:
0 = IM = Asynchronous Induction
Motor
1 = PMM = PM Synchronous Motor
Description
Motor noise can be minimized using a
high switching frequency. Increasing the
switching frequency reduces the
capacity of the drive. It is recommended
to use a lower frequency when the motor
cable is long in order to minimize
capacitive currents in the cable.
Prevents the drive from tripping when a
motor switch is located between the
drive and motor.
0 = No
1 = Yes
Defines the zero frequency voltage of
the U/f curve.