Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
Address
16-bit
32-bit
2106
2107
2108
2109
2110
2111
Status Word bits
The Status word is composed of 32 bits. The bits are described in the following table.
Bit
Name
B0
Ready
B1
Run
B2
Direction
B3
Fault
B4
Alarm
B5
AtReference
B6
ZeroSpeed
B7
FluxReady
B8-B28
Not used
B29 Control place
B30 Control place
0
0
0
1
0
1
1
0
The use of process data depends on the application. In a typical situation, the device is started and stopped with
the ControlWord (CW) written by the Master and the Rotating speed is set with Reference (REF). With PD1
through PD8 the device can be given other reference values (for example, Torque reference).
With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value (ACT) and PD1
through PD8 show the other actual values.
144 | 180
Siemens Industry, Inc.
Building Technologies
Name
2159 = High data
FB Process Data Out 3
2160 = Low data
2161 = High data
FB Process Data Out 4
2162 = Low data
2163 = High data
FB Process Data Out 5
2164 = Low data
2165 = High data
FB Process Data Out 6
2166 = Low data
2167 = High data
FB Process Data Out 7
2168 = Low data
2169 = High data
FB Process Data Out 8
2170 = Low data
Table 117: Status Word Bits B1-B28.
Value 1
Ready
Not ready
Running
Stop
Counterclockwise
Clockwise
Faulted
Not faulted
Alarm
No alarm
True
False
True
False
True
False
Table 118: Status Word Bits B29-B31, Descriptions of Bit Connections.
B31 Control place
1
0
1
0
Siemens BT300 HVAC Drive
User-definable.
User-definable.
User-definable.
User-definable.
User-definable.
User-definable.
Value 0
Description
Indicates whether the drive is
ready or not.
Indicates whether the drive is
running or stopped.
Indicates the rotation direction of
the motor.
Indicates if a fault is active.
Indicates if an alarm is active.
Reference frequency reached.
Motor running at zero speed.
Motor is magnetized.
Description
Fieldbus
Keypad
PC tool
I/O terminals
Range/Type
DPD01809
2016-06-07

Hide quick links:

Advertisement

Table of Contents
loading