P1200
5
6
Table 6- 47
Parameter Description
P1202 =
...
P1203 =
...
Note
The higher the search rate (P1203), the longer the search time. A lower search rate shortens
the search time.
The "flying restart" function decelerates the motor slightly. The smaller the drive torque, the
more the drive is decelerated.
The "flying restart" function should not be activated for motors in group drives due to the
different coasting characteristics of the individual motors.
6.9.4
PID technology controller
Technology controller for processing higher-level control functions
The technology controller supports all kinds of simple process control tasks. For example, it
is used for controlling pressures, levels, or flow rates.
SINAMICS G110D
Operating Instructions, 2009-05-15, A5E02385577A AB
Flying restart active
Flying restart is active after
Power ON
•
Faults
•
OFF2
•
Flying restart is active after
Faults
•
OFF2
•
Additional commissioning parameters
Motor current: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Defines the search current with respect to the rated motor current (P0305) that is
present when the "flying restart" function is used.
Search rate/speed: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Sets the factor by which the output frequency changes during the flying restart to
synchronize itself with the running motor.
6.9 Technological functions
Search direction
Search performed in direction of setpoint only
Search performed in direction of setpoint only
Functions
127