Parameters (M3)
Slot A Basic (M3.5.4.1)
Structure
Parameter
P3.5.4.1.1
AO1 Function
P3.5.4.1.2
AO1 Filter Time
P3.5.4.1.3
AO1 Min Signal
P3.5.4.1.4
AO1 MinScale
P3.5.4.1.5
AO1 MaxScale
Settings
0
0% Test
1
100% Test
2
Output Frequency
3
Freq Reference
4
Motor Speed
5
Output Current
6
Motor Torque
7
Motor Power
8
Motor Voltage
9
DC Link Voltage
10
PID 1 Output
11
PID 2 Output
12
Process Data In 1
13
Process Data In 2
14
Process Data In 3
15
Process Data In 4
16
Process Data In 5
17
Process Data In 6
18
Process Data In 7
19
Process Data In 8
64 | 180
Siemens Industry, Inc.
Building Technologies
NOTE:
The status of the Analog Outputs can be monitored in the Multimonitor (P2.1) view, or
in the I/O and Hardware (M5) menu.
Table 38: Analog Outputs, Slot A (Basic).
Unit
Min
Max
0% Test
ProcessDataIn8
s
0
300
0 Vdc/0 mA
2 Vdc/4 mA
Varies
Varies
Varies
Varies
Table 39: Analog Output Functions.
AO is not used. 0 output.
AO is max. 10 Vdc or 20 mA output.
Track the Output Frequency based on 0 to Max Frequency (P3.3.2).
Track the Frequency Reference base on 0 to Max Frequency (P3.3.2).
Track the Motor Speed based on 0 to Motor Nom Speed (P3.1.1.3).
Track the Output Current based on 0 to Motor Nom Currnt (P3.1.1.4).
Track the Motor Torque based on 0 to TnMotor.
Track the Motor Power based on 0 to PnMotor.
Track the Motor Voltage based on 0 to VnMotor.
Track the DC Link Voltage based on 0 - 1000 Vdc.
Track the PID1 Output based on 0 - 100%
Track the PID2 Output based on 0 - 100%.
Track the Process Data In 1 where 5000 = 50.00%.
Track the Process Data In 2 where 5000 = 50.00%.
Track the Process Data In 3 where 5000 = 50.00%.
Track the Process Data In 4 where 5000 = 50.00%.
Track the Process Data In 5 where 5000 = 50.00%.
Track the Process Data In 6 where 5000 = 50.00%.
Track the Process Data In 7 where 5000 = 50.00%.
Track the Process Data In 8 where 5000 = 50.00%.
Siemens BT300 HVAC Drive
Default
ID
Output
10050
See
Frequency
1
10051
Filter time of analog output signal
0 = No filtering
0 Vdc/0 mA
10052
Settings:
0 = 0 Vdc/0 mA
1 = 2 Vdc/4 mA
Varies
10053
Min Scale in process unit.
Varies
10054
Max Scale in process unit